孝感市(shi)自來水(shui)公司依(yi)據《給(gei)水(shui)排水(shui)管道(dao)(dao)工程施(shi)工及(ji)驗(yan)收(shou)規(gui)(gui)范》(GB?50268—2008)、《室(shi)外給(gei)水(shui)設計規(gui)(gui)范》及(ji)省、市(shi)有關(guan)規(gui)(gui)定,對供水(shui)管道(dao)(dao)工程的驗(yan)收(shou)進行(xing)(xing)了規(gui)(gui)范和說明,以后的新接供水(shui)工程驗(yan)收(shou),均按照該《制度》執行(xing)(xing)。

公司(si)成立由(you)分管(guan)經理擔任組(zu)長的工(gong)程驗(yan)(yan)收小組(zu),由(you)工(gong)程管(guan)理部(bu)牽頭組(zu)織實(shi)(shi)施,管(guan)安公司(si)、技術信息部(bu)、供水稽查部(bu)、物資(zi)管(guan)理部(bu)、水表檢定(ding)站、報(bao)裝(zhuang)辦、二供辦、營業所等(deng)相關部(bu)門依據國(guo)家《給水排水管(guan)道(dao)工(gong)程施工(gong)及(ji)驗(yan)(yan)收規(gui)范》中規(gui)定(ding)的相關細(xi)則進行(xing)工(gong)程驗(yan)(yan)收,驗(yan)(yan)收過程需由(you)區市(shi)政(zheng)質量監(jian)督部(bu)門參(can)與的,由(you)監(jian)督部(bu)門參(can)與過程監(jian)督。為保證(zheng)驗(yan)(yan)收工(gong)作(zuo)的各個(ge)環(huan)節落實(shi)(shi)到(dao)位(wei),公司(si)制定(ding)了《報(bao)裝(zhuang)接水工(gong)程驗(yan)(yan)收管(guan)理規(gui)定(ding)》,并就規(gui)定(ding)的制定(ding)依據、驗(yan)(yan)收程序(xu)及(ji)標(biao)準(zhun)、驗(yan)(yan)收要求、整(zheng)改措施、參(can)驗(yan)(yan)單位(wei)代表簽字(zi)、驗(yan)(yan)收資(zi)料存檔等(deng)方面作(zuo)了較詳細(xi)的規(gui)定(ding)。

一(yi)、工程竣(jun)工后,應依據工程施工設計方案,按照國家有關技術標準和規范組織驗收,未經驗收或驗收不(bu)合(he)格(ge)的不(bu)準投入使用(yong)。

二(er)、現(xian)場驗收合格(ge)的(de)工程項目(mu)應達到(dao)下列要(yao)求:

1、使(shi)用的管(guan)材、閘閥、水表、表箱的產品標準和生產廠家應與設(she)計要(yao)求一致,并有產品質量檢驗合格證(zheng)書。

2、管網的走向(xiang)、口徑應與施工圖設計一致。

3、路面的恢復(fu)應平整、堅固(gu),不影響(xiang)路面正常功能。

4、閘閥井(jing)(jing)、水(shui)表井(jing)(jing)的大小、井(jing)(jing)深應(ying)滿足正(zheng)常作業要求,水(shui)表井(jing)(jing)、閘閥井(jing)(jing)應(ying)有濾水(shui)功能(neng)。

5、防凍水表(biao)箱的安(an)裝位置適當,結構密封(feng)、牢(lao)固(gu)(gu);戶外(wai)立管(guan)(guan)應(ying)有防凍、防曬(shai)套管(guan)(guan),管(guan)(guan)卡應(ying)牢(lao)固(gu)(gu)。

6、經水壓試驗合格,施工資料準確(que)、詳實。

三、工程(cheng)驗收(shou)過程(cheng)中,驗收(shou)專(zhuan)班應(ying)對工程(cheng)材料質量(liang)進行認真核查(cha)。供水(shui)工程(cheng)及(ji)(ji)供水(shui)設施(包括二次供水(shui)設施)所使用的材料、設備及(ji)(ji)管(guan)(guan)材、管(guan)(guan)件(jian)、配件(jian)等必(bi)須(xu)符合國家相關質量(liang)標(biao)準。

1、工(gong)程采用的(de)管材和管件,應符合相關(guan)產(chan)(chan)品現行質量標(biao)(biao)準的(de)要求,產(chan)(chan)品標(biao)(biao)稱的(de)允許工(gong)作壓力應大(da)于管道和管件使用區域的(de)最大(da)工(gong)作壓力。

2、同(tong)一處工程使(shi)用(yong)的管(guan)材(cai)和管(guan)件,原則上應(ying)使(shi)用(yong)同(tong)一廠家的配套產品。

 3、埋地(di)管道(dao)采(cai)用的管材和管件(jian),應具有耐腐蝕和能承(cheng)受(shou)相應地(di)面荷(he)載能力(li)。

4、管道上(shang)使(shi)用(yong)的(de)各類閥(fa)門的(de)材質,應耐腐蝕和耐壓(ya),并根據管徑大小(xiao)和所承受壓(ya)力的(de)等級及(ji)使(shi)用(yong)溫度選擇優質產(chan)品(pin)。

5、地(di)上(shang)式(shi)水表集裝箱的材質必須具備防銹功能,地(di)下式(shi)水表箱(池(chi))的箱蓋應(ying)便(bian)于啟閉,水表箱內(nei)的設(she)施布置應(ying)方便(bian)檢(jian)修。

四、工(gong)(gong)(gong)程(cheng)施工(gong)(gong)(gong)必(bi)須嚴(yan)格按照(zhao)施工(gong)(gong)(gong)設(she)計施工(gong)(gong)(gong),管道及附屬設(she)施的安裝(zhuang)應(ying)充分考慮便(bian)于水(shui)表查(cha)抄(chao)與設(she)施維護。工(gong)(gong)(gong)程(cheng)驗收過程(cheng)中(zhong),驗收專班應(ying)嚴(yan)格按照(zhao)工(gong)(gong)(gong)程(cheng)施工(gong)(gong)(gong)設(she)計文件,認真核查(cha)施工(gong)(gong)(gong)日(ri)志,對安裝(zhuang)質(zhi)量(liang)進行檢查(cha)。

1、管(guan)溝內敷設(she)(she)的室外給(gei)水管(guan)道,管(guan)溝的地基(ji)要牢固、平整,防止因地層沉降導致管(guan)道斷裂。塑(su)料管(guan)道不得露(lu)天架空(kong)敷設(she)(she),確(que)需架空(kong)鋪設(she)(she)時(shi)應采(cai)取(qu)保溫(wen)和防曬(shai)措施(shi)。

2、埋(mai)地給(gei)水(shui)管道(dao)的(de)覆土(tu)埋(mai)深一般不(bu)得(de)(de)小(xiao)于(yu)(yu)500mm,穿越道(dao)路的(de)管道(dao)埋(mai)深不(bu)得(de)(de)小(xiao)于(yu)(yu)700mm。給(gei)水(shui)系統各(ge)種井室(shi)內的(de)管道(dao)安裝應充分(fen)考慮檢修維護的(de)需(xu)要,其井壁距(ju)法蘭(lan)或承口的(de)距(ju)離,當(dang)(dang)管徑小(xiao)于(yu)(yu)或等(deng)于(yu)(yu)450mm時(shi),不(bu)得(de)(de)小(xiao)于(yu)(yu)250mm;當(dang)(dang)管徑大(da)于(yu)(yu)450mm時(shi),不(bu)得(de)(de)小(xiao)于(yu)(yu)350mm。

3、給(gei)水管道不得(de)直接穿(chuan)越污水井、化(hua)糞池、公共廁所(suo)等污染(ran)源。

4、管道接口法蘭、卡(ka)(ka)扣、卡(ka)(ka)箍(gu)等應(ying)安裝在檢查井(jing)或地溝(gou)內(nei),不得直(zhi)接覆(fu)埋于土壤中。

5、住宅小(xiao)區(qu)的(de)室(shi)外(wai)給水管道,原則上應(ying)沿小(xiao)區(qu)道路平行(xing)于建筑敷設(she),與建筑物外(wai)墻的(de)凈距一般不宜小(xiao)于1m;與其(qi)它地下管線和(he)喬(qiao)木的(de)間(jian)距應(ying)符合相關(guan)規(gui)定(ding)。

6、管道(dao)連接應(ying)符合工藝要求(qiu),閥(fa)門、水(shui)表等(deng)安裝位置應(ying)正確。塑(su)料(liao)給水(shui)管道(dao)上的水(shui)表、閥(fa)門等(deng)設施,其(qi)重量(liang)或(huo)啟閉裝置的扭矩不得作用于管道(dao),當管徑(jing)大于50mm時須設獨立支承裝置。

7、主要(yao)管線應設立地標,地標標識的管線必(bi)須(xu)準確無誤。

8、水表(biao)箱(xiang)應安(an)裝在便于抄表(biao)的(de)位(wei)置,盡量(liang)避免安(an)裝在樓道、灶臺下(xia)或(huo)冬季主導風向位(wei)置;地下(xia)式水表(biao)箱(xiang)應充(chong)分考慮(lv)濾水和防凍。

9、進水(shui)總表和住(zhu)宅進戶水(shui)表前一般(ban)應(ying)設(she)置(zhi)管道過濾器;給(gei)水(shui)加(jia)壓系統應(ying)設(she)置(zhi)水(shui)錘消(xiao)除裝置(zhi)。

五、供水工(gong)程完(wan)成安(an)裝(zhuang)后必須(xu)進行(xing)水壓試(shi)驗,其試(shi)驗壓力(li)為工(gong)作壓力(li)的1.5倍,但不得小于0.6MPA。工(gong)程量(liang)較大的,可(ke)在安(an)裝(zhuang)施工(gong)過程中進行(xing)階段性試(shi)壓,其試(shi)壓記(ji)錄必須(xu)真實、完(wan)整(zheng)。

無試壓記錄(lu)或試壓不(bu)合格的,不(bu)予驗收。

六、給水管道(dao)在竣工后,必(bi)須對管道(dao)進行(xing)沖洗,并對水質進行(xing)抽樣檢測。

七(qi)、有下列情形之(zhi)一的(de),驗收(shou)專班應不予(yu)現(xian)場(chang)驗收(shou),并責(ze)令限期(qi)整(zheng)改(gai),待完成工程整(zheng)改(gai)后,重(zhong)新組織驗收(shou):

1、工程(cheng)使用(yong)的材料質量抽查不(bu)合格(ge)或不(bu)符合設計文(wen)件要求的。

2、未按設計文件(jian)要求施工或(huo)安裝質量未達到相關標準的(de)。

3、水壓(ya)試驗不合格的。

4、水質(zhi)抽樣檢查不(bu)合(he)格的。

5、施工日志不真(zhen)實、不完(wan)整的。